Let us have total load of 16 kW with 0.8 pf, which needs to be supported by battery backup for at least 1 hr, when the grid fails. Before choosing the battery with respect to cost or brand, there are many questions to be answered
Battery sizing calculation differs with respect to application as well
Battery load of UPS should be calculated by considering the following 4 margin factors as shown below
Actual load / Inverter Efficiency = Nominal battery load
Temperature correction factor x Design Margin x Aging Margin x Overloading factor = Battery load
Selected Battery type Sealed Maintanence Free VRLA.
UPS Output rating = 20 kVA
Output Power Factor = 0.8
Actual Load = 16 kW
Inverter Efficiency (EFF) = 94%
Nominal Battery load = 17.02 kW
Temperature correction factor for 25°C = 1.00
Design Margin = 1.10
Aging Margin = 1.25
Overloading Factor = 1.10
Calculated Battery load = 25.74 kW
End Cell Voltage (ECV) should be maintained
well within the voltage window of the UPS.
Nominal DC voltage = 400 Vdc
Maximum Rectifier equalizing voltage = 432 Vdc
Inverter low voltage cut-off = 290 Vdc
Voltage drop of DC cables is assumed = 2 Vdc
Minimum required UPS voltage = 292 Vdc
Boost charge = 2.4 Vdc
Equalizing Cell Voltage = 2.25 Vdc
End cell Voltage (ECV) Selected = 1.75 V/Cell
Nominal Cell Voltage = 2 V/Cell
Battery Model Selected = LX-12 150
Total No.of cell x ECV > Cut-off voltage
Let us assume 1 hr be the required backup time
Minimum number of cells required = 166.86 Nos.
Total number of cells selected = 180.00 Nos.
Backup time = 60 mins.
Required cell discharge for 1hrs in Watts = 143.03 W/cell
Available cell discharge for 1hrs in Watts = 203 W/cell
No.of strings = 1 Nos.
Number of cells per bloc = 6 Nos.
As the selected battery bloc is 12V
(Total No.of 2V cells) / 6 = No.of Blocs
180/6 = 30
Number of blocs required = 30 Nos.